Solar thermal energy transforms solar radiation into heat. In buildings it is mainly used to produce domestic hot water, heat swimming pools and, in certain cases, support low-temperature heating systems.
It should not be confused with photovoltaics, which generates electricity. It is also not the same as a concentrated solar thermal power plant: a domestic installation normally works at low temperatures and is sized for a specific thermal demand.
How a solar thermal installation works
- Sensors: They absorb radiation and transfer heat to a fluid.
- Primary circuit: transports energy from the collectors. It is usually a closed circuit with water and antifreeze.
- Exchanger: separates the fluid of the solar circuit from the drinking water and transmits the heat.
- Accumulator: stores hot water to decouple intake and demand.
- Regulation and security: differential control, pumps, expansion vessel, valves, drains and protection against overtemperature.
- Auxiliary system: completes the demand when the available solar energy is not enough.
Types of collector
| Sensor | Regular use | Relevant aspects |
|---|---|---|
| unglazed | Heating of outdoor pools | Simple and efficient when the required temperature is close to the outside temperature |
| flat plate | DHW, indoor pool and low temperature support | Usual solution; performance, cost and risk of stagnation must be balanced |
| vacuum tubes | Higher temperature demands or high loss conditions | Good insulation of the absorber, with specific cost and maintenance |
The most sophisticated sensor is not always the most convenient. Selection depends on working temperature, weather, orientation, shadows, available space, demand and architectural integration.
Natural or forced circulation
In a system thermosiphon, the fluid circulates due to differences in density and the accumulator must be located above the collector. It is a compact solution, but its position, weight, integration and external exposure may limit it.
In a facility of forced circulation, a pump moves the fluid when the collector can deliver useful heat to the accumulator. It allows greater freedom of design and control, although it incorporates electricity, regulation and more elements to maintain.
Building applications
- Domestic hot water: most common application due to its demand throughout the year.
- Swimming pools: especially effective when the required temperature is moderate.
- Heating: can support low temperature systems, but the gap between greater winter demand and greater summer production requires careful study.
- Solar cooling: possible through absorption or desiccant systems, normally in larger scale and more complex installations.
Solar thermal can be combined with heat pumps, biomass, boilers, thermal networks or renewable electricity production. There is no general incompatibility with cogeneration: compatibility depends on the hydraulic scheme, temperatures, regulation and priority of each source.
What to check before installing
- Monthly DHW demand and real usage profile.
- Available radiation, orientation, tilt and shadows.
- Working temperatures and accumulation volume.
- Losses in pipes, accumulation and recirculation.
- Risk of frost, stagnation and overtemperature in periods without consumption.
- Space, weight, maintenance access and integration into the roof or façade.
- Technical and economic comparison with other renewable solutions.
Regulations and renewable contribution
Section HE 4 of the Technical Code regulates the minimum contribution of renewable energy for DHW and air conditioning of indoor swimming pools in the cases included in its scope. It currently establishes, in general terms, a minimum renewable contribution of 70%, which can be reduced to 60% when the demand for DHW is less than 5,000 liters per day.
The requirement does not require it to be resolved exclusively with solar thermal. It can be fulfilled through different renewable sources if the contribution, performance and established conditions are justified. In addition, the RITE, health regulations and applicable ordinances must be verified.
Essential maintenance
- Check pressure, tightness and condition of the heat transfer fluid.
- Check pumps, probes, regulation and expansion tank.
- Inspect insulation of pipes, supports and fixings.
- Check scale, anodes and condition of the accumulator.
- Check protection against frost and overtemperature.
The Basic Document HE of the CTE includes the required renewable contribution. The IDAE guide for rehabilitation of solar thermal installations develops inspection, maintenance and fault correction criteria.
Are you renovating a home or its ACS installation?
I can compare solar thermal, heat pump and other alternatives according to demand, space, investment and maintenance, and integrate them correctly into the project.